Water Leakage Detector System protects facilities such as computer rooms, critical facilities, warehouses, and critical document rooms from water leaks and flooding accidents. The System is composed of at least one line type sensor that quickly detects water leaks along with a water leakage detector that alerts the water leaks to the user in a timely manner.

Water leak location is electronically measured and digitally displayed at units of 1 meter. Furthermore, when a water leak occurs, the sensor uses a colored display, making an on-site visual confirmation easy and making it possible to identify the location of the leak more quickly.

We offers the following water leakage detector & sensors as standard set, which are in control of one circuits according to the user's requirement. Each model incorporates a non-voltage output terminal that can be connected to a central monitoring panel.

 

Product Specification//

There are 3 Components inside the package. 

  

- Detector

TATSUTA AD-AS-1DM detector can be mounted to the DIN track in the panel and connected with DC power. 

Model

TATSUTA AD-AS-1DM

Number of sensor circuits

1 circuit

Rated Voltage

AC24V±10%(for 50Hz/60Hz)

DC24V±10%

Voltage across sensor

AC5.3V

Water leakage alarm indicator

Orange LED flash

Break alarm indicator

Orange LED flash

Control output Contacts

AC125V 0.2A DC30V 1.0A

Power Consumption

3W max.

Set sensitivity

4 level

Outside dimensions W×H×D(mm)

22×28×59

Weight(kg)

0.059

 

- Sensor

 

TATSUTA AD-S Sensor is the non-coloring water leakage sensor which promptly detects any water leak.

Model

TATSUTA AD-S Sensor (Non-coloration model)

Construction

Material: Strand of tinned annealed copper wires

Composition: Copper wire 0.18 mm in diameter × 13 (0.33 mm2 )

Electrode resistance(DC)

 

Standard: 26.6 Ω/km (20°C)

Resistance between electrodes(AC)

50kΩmin.

Insulation performance

Insulation resistance between electrodes is 10 MΩ min. when measured with a 100 VDC Insulation Tester.

Sensitivity (Water absorptivity)

Resistance between electrodes is 5 kΩ max. when water absorption is 3.0 ml or less. (Tap water is allowed to drop at a rate of 0.05 ml/s directly on the sensor.)

Moisture resistance between electrodes

Resistance between electrodes is 50 kΩ min. even in a highly humid environment but without dew condensation.

Reusability

After leakage detection, the sensor is reset and can be reused within 30 min if it is retained under normal conditions (i.e., not exposed to water). The sensor cannot be reused if it has absorbed water that contains conductive or water-repellent material.

Heat resistance

60°C max. for continuous operation.

Radiation resistance

No performance deterioration (water absorptivity, moisture resistance, and mechanical properties) results after exposure to 50 Mrad(Note) .

Weight

10.5±1.0 g/m

Length

10m

(Note) Estimated quantity of radiation to which electric cables can be exposed Over the period of 40 years, which is the designed service life of a typical nuclear power plant.

 

- Wire Disconnection Detection Terminal

This is a sensor terminal used for on-site installation.

Model

TATSUTA ZT-2

Number

1

Item Specification

 

Use parts:

1-Lead Wire: PVC UL1015LF 22AWG WHITE

2-Resistor: 20kΩ±2% 1/4W metal film resistor

3-Solder: Pb-free solder

4-Cap: PVC tube

5-Filling thing: Silicone rubber

Resistance between electrodes (AC)

20kΩ±1%

Moisture resistivity

 

Resistance between electrodes is 20kΩ±10% under heavy wet condition, expecting dew condensing environment.

Heat resistivity

60 max. for continuous operation.

Weight:

3.2g±0.8g